01.08

Output Frequency Lower Limit

Settings
The Upper/Lower Limits are to prevent operation errors and machine damage.
If the Output Frequency Upper Limit is 50Hz and the Maximum Output Frequency is 60Hz, the
Output Frequency will be limited to 50Hz.
If the Output Frequency Lower Limit is 10Hz, and the Minimum Output Frequency (Pr.01.05) is
set to 1.0Hz, then any Command Frequency between 1.0-10Hz will generate a 10Hz output
from the drive.
This parameter must be equal to or less than the Output Frequency Upper Limit (Pr.01.07).
The Output Frequency Lower Limit value = (Pr.01.00 * Pr.01.08) /100.
01.09
Acceleration Time 1 (Taccel 1)
01.10
Deceleration Time 1 (Tdecel 1)
01.11
Acceleration Time 2 (Taccel 2)
01.12
Deceleration Time 2 (Tdecel 2)
Settings
Acceleration/deceleration time 1 or 2 can be switched by setting the external terminals MI3~
MI12 to 7 (set Pr.04.05~Pr.04.08 to 7 or Pr.11.06~Pr.11.11 to 7).
01.19

Accel/Decel Time Unit

Settings
4-44
01.08
Output Frequency
Voltage
Lower Limit
01.02
Maximum
Output
Voltage
01.04
Mid-point
Voltage
01.06
Minimum
01.05
01.03
Output
Mid-point
Minimum
Voltage
Freq.
Output
Freq.
0.0 to 100.0%
0.1 to 600.0 sec / 0.01 to 600.0 sec
0
Unit: 0.1 sec
1
Unit: 0.01 sec
01.07
Output Frequency
Upper Limit
The limit of
Output
Frequency
01.01
Maximum Voltage
Frequency
(Base Frequency)
V/f Curve
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
Frequency
01.00
Maximum
Output
Frequency
Factory Setting: 0.0
Unit: 0.1/0.01
Unit: 0.1/0.01
Unit: 0.1/0.01
Unit: 0.1/0.01
Factory Setting: 10.0
Factory Setting: 0
Unit: 0.1