Keypad Frequency Command; Communication Frequency Command; The Selections For Saving Keypad Or Communication Frequency Command; Initial Frequency Selection - Delta Electronics AC Motor Drive VFD-E User Manual

Vfd-e high performance/flexible options/micro type ac motor drives
Table of Contents

Advertisement

When Pr.02.07 is set to 1: increase/decrease the frequency by acceleration/deceleration
settings. It is valid only when the AC motor drive is running.
When Pr.02.07 is set to 2: increase/decrease the frequency by Pr.02.08.
When Pr.02.07 is set to 3: increase/decrease the frequency by Pr.02.08 (unit: pulse input).
02.11

Keypad Frequency Command

Settings
This parameter can be used to set frequency command or read keypad frequency command.
02.12

Communication Frequency Command

Settings
This parameter can be used to set frequency command or read communication frequency
command.
The Selections for Saving Keypad or Communication Frequency
02.13
Command
Settings
This parameter is used to save keypad or RS-485 frequency command.
02.14
Initial Frequency Selection (for keypad & RS485/USB)
Settings
02.15
Initial Frequency Setpoint (for keypad & RS485/USB)
Settings
These parameters are used to determinate the frequency at stop:
When setting Pr.02.14 to 0: the initial frequency will be current frequency.
When setting Pr.02.14 to 1: the initial frequency will be 0.
When setting Pr.02.14 to 2: the initial frequency will be Pr.02.15.
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
0.00 to 600.0Hz
0.00 to 600.0Hz
0
Save Keypad & Communication Frequency
1
Save Keypad Frequency only
2
Save Communication Frequency only
0
By Current Freq Command
1
By Zero Freq Command
2
By Frequency Display at Stop
0.00 ~ 600.0Hz
Chapter 4 Parameters|
Factory Setting: 60.00
Factory Setting: 60.00
Factory Setting: 0
Factory Setting: 0
Factory Setting: 60.00
Unit: 0.01
Unit: 0.01
Unit: 0.01
4-59

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents