Parameter Reset

00-02
Control
VF
VFPG
mode
Settings
When it is set to 1, all parameters are read only except Pr.00-00~00-07 and it can be used
with password setting for password protection.
This parameter allows the user to reset all parameters to the factory settings except the fault
records (Pr.06-17 ~ Pr.06-22).
50Hz: Pr.01-01 is set to 50Hz and Pr.01-02 is set to 230V or 400V.
60Hz: Pr.01-01 is set to 60Hz and Pr.01-02 is set to 230Vor 460V.
When Pr.00-02=08, the KPV-CE01 keypad is locked and only Pr.00-02 can be set. To unlock
the keypad, set Pr.00-02=00.
When Pr.00-02 is set to 1 or 8, Pr.00-02 setting should be set to 0 before setting to other
setting.
After setting Pr.00-02 to 2, it can display group 11 to re-connect the keypad after disconnection
or re-power on after the power off.
Start-up Display Selection
00-03
Control
VF
VFPG
mode
Settings 0
1
2
3
This parameter determines the start-up display page after power is applied to the drive.
00-04

Content of Multi-Function function Display

Control
VF
VFPG
mode
Revision August 2008, 03VE, SW V2.04
SVC
FOCPG TQRPG
0
No Function
1
Read Only
2
Enable Group 11 Parameters Setting
8
Keypad Lock
9
All parameters are reset to factory settings (50Hz, 220V/380V)
10 All parameters are reset to factory settings (60Hz, 220V/440V)
SVC
FOCPG TQRPG
Display the frequency command value. (LED F)
Display the actual output frequency (LED H)
Multifunction display, see Pr.00-04 (LED U)
Display the output current (A)
SVC
FOCPG TQRPG
Chapter 4 Parameters|
Factory setting: 0
Factory setting: 0
Factory setting: 0
4-39