Group 6 Protection Parameters - Delta Electronics AC Motor Drive VFD-VE Series User Manual

Vfd-ve series high performance field oriented control ac motor drive
Table of Contents

Advertisement

Group 6 Protection Parameters

Pr.
Explanation
Low Voltage Level
06-00
Over-voltage Stall
06-01
Prevention
Phase-loss Protection
06-02
Over-current Stall
06-03
Prevention during
Acceleration
Over-current Stall
06-04
Prevention during
Operation
Accel./Decel. Time
06-05
Selection of Stall
Prevention at constant
speed
Over-torque Detection
06-06
Selection (OT1)
Over-torque Detection
06-07
Level (OT1)
Over-torque Detection
06-08
Time (OT1)
Over-torque Detection
06-09
Selection (OT2)
Over-torque Detection
06-10
Level (OT2)
Over-torque Detection
06-11
Time (OT2)
Current Limit
06-12
Electronic Thermal
06-13
Relay Selection (Motor
1)
Electronic Thermal
06-14
Characteristic for
Motor 1
Heat Sink Over-heat
06-15
(OH) Warning
Stall Prevention Limit
06-16
Level
06-17
Present Fault Record
Second Most Recent
06-18
Fault Record
Third Most Recent
06-19
Fault Record
06-20
Fourth Most Recent
Fault Record
Revision August 2008, 03VE, SW V2.04
Settings
160.0~220.0Vdc
320.0~440.0Vdc
0.0: Disable
350.0~450.0Vdc
700.0~900.0Vdc
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
00~250%
00~250%
0: by current accel/decel time
1: by the 1st accel/decel time
2: by the 2nd accel/decel time
3: by the 3rd accel/decel time
4: by the 4th accel/decel time
5: by auto accel/decel time
0: disable
1: over-torque detection during constant speed
operation, continue to operate after detection
2: over-torque detection during constant speed
operation, stop operation after detection
3: over-torque detection during operation, continue to
operate after detection
4: over-torque detection during operation, stop
operation after detection
10~250%
0.0~60.0 sec
0: disable
1: over-torque detection during constant speed
operation, continue to operate after detection
2: over-torque detection during constant speed
operation, stop operation after detection
3: over-torque detection during operation, continue to
operate after detection
4: over-torque detection during operation, stop
operation after detection
10~250%
0.0~60.0 sec
0~250%
0: Inverter motor
1: Standard motor
2: Disable
30.0~600.0 sec
0.0~110.0 °C
0~100% (refer to Pr.06-03, Pr.06-04)
0: No fault
1: Over-current during acceleration (ocA)
2: Over-current during deceleration (ocd)
3: Over-current during constant speed (ocn)
4: Ground fault (GFF)
5: IGBT short-circuit (occ)
6: Over-curent at stop (ocS)
7: Over-voltage during acceleration (ovA)
8: Over-voltage during deceleration (ovd)
9: Over-voltage during constant speed (ovn)
10: Over-voltage at stop (ovS)
Chapter 4 Parameters|
Factory
VF
VFPG SVC
Setting
180.0
360.0
380.0
760.0
0
170
170
0
0
150
0.1
0
150
0.1
150
2
60.0
85.0
50
0
0
0
0
FOCPG TQRPG
4-13