Delta Electronics AC Motor Drive VFD-VE Series User Manual page 110

Vfd-ve series high performance field oriented control ac motor drive
Table of Contents

Advertisement

13: cancel the setting of the optimal
acceleration/deceleration time
14: switch between drive settings 1 and 2
15: operation speed command form AVI
16: operation speed command form ACI
17: operation speed command form AUI
18: Emergency Stop (07-36)
19: Digital Up command
20: Digital Down command
21: PID function disabled
22: clear counter
23: input the counter value (multi-function input command
6)
24: FWD JOG command
25: REV JOG command
26: TQC+PG/FOC+PG model selection
27: ASR1/ASR2 selection
28: Emergency stop (EF1)
29: Signal confirmation for Y-connection
30: Signal confirmation for
31: High torque bias (by Pr.07-29)
32: Middle torque bias (by Pr.07-30)
33: Low torque bias (by Pr.07-31)
34: Enable multi-step position control
35: Enable position control
36: Enable position learning function (valid at stop)
37: Enable pulse position input command
38: Disable write EEPROM function
39: Torque command direction
40: Force stop
41: Serial position clock
42: Serial position input
43: Analog input resolution selection
44: Reset initial reel diameter
45: Reset initial reel diameter 0
46: Reset initial reel diameter 1
47: Reset PID control integration of tension
48: Mechanical Gear Ratio Switch
49: Reserved
50: Reserved
This parameter selects the functions for each multi-function terminal.
The terminals of Pr.02-23~Pr.02-27 are virtual and set as MI7~MIB when using with optional
card EMV-APP01
If Pr.02-00 is set to 3-wire operation control. Terminal MI1 is needed for the 3
Therefore, MI1 is not allowed for any other operation.
Multi-function input commands 7-14 are the extension terminals of Pr.02-01 to Pr.02-06. There
are 14 terminals but the terminals 7-14 are virtual terminals and you can set the status of bit 8-
15 of Pr.02-10 to ON or OFF by KPV-CE01 or communication.
Revision August 2008, 03VE, SW V2.04
Settings
  connection
Chapter 4 Parameters|
Control Mode
VF
VFPG
SVC
FOCPG TQRPG
rd
wire position.
4-61