Base Block Speed Search; Auto Restart After Fault; Speed Search During Start-Up - Delta Electronics AC Motor Drive VFD-VE Series User Manual

Vfd-ve series high performance field oriented control ac motor drive
Table of Contents

Advertisement

07-10

Base Block Speed Search

Control
VF
mode
Settings
This parameter determines the AC motor drive restart method after External Base Block is
enabled.
In PG control mode, the AC motor drive will execute the speed search function automatically
by the PG speed when this setting isn't set to 0.
07-11

Auto Restart After Fault

Control
VF
VFPG
mode
Settings
Only after an over-current OC or over-voltage OV fault occurs, the AC motor drive can be
reset/restarted automatically up to 10 times.
Setting this parameter to 0 will disable the reset/restart operation after any fault has occurred.
When enabled, the AC motor drive will restart with speed search, which starts at the frequency
before the fault. To set the waiting time before restart after a fault, please set Pr. 07-08 Base
Block Time for Speed Search.
07-12

Speed Search during Start-up

Control
VF
VFPG
mode
Settings
This parameter is used for starting and stopping a motor with high inertia. A motor with high
inertia will take a long time to stop completely. By setting this parameter, the user does not
need to wait for the motor to come to a complete stop before restarting the AC motor drive. If a
PG card and encoder is used on the drive and motor, then the speed search will start from the
speed that is detected by the encoder and accelerate quickly to the commanded frequency.
The output current is set by the Pr.07-09.
Revision August 2008, 03VE, SW V2.04
VFPG
SVC
FOCPG TQRPG
0
Stop operation
1
Speed search starts with last frequency command
2
Speed search starts with minimum output frequency
SVC
FOCPG TQRPG
0 to 10
SVC
FOCPG TQRPG
0
Disable
1
Speed search from maximum frequency
2
Speed search from start-up frequency
3
Speed search from minimum frequency
Chapter 4 Parameters|
Factory Setting: 0
Factory Setting: 0
Factory Setting: 0