Pg Feedback Fault Treatment; Detection Time For Pg Feedback Fault; Asr (Auto Speed Regulation) Control (P) 1; Asr (Auto Speed Regulation) Control (I) 1 - Delta Electronics AC Motor Drive VFD-VE Series User Manual

Vfd-ve series high performance field oriented control ac motor drive
Table of Contents

Advertisement

10-02

PG Feedback Fault Treatment

Control
VFPG FOCPG TQRPG
mode
Settings
10-03

Detection Time for PG Feedback Fault

Control
VFPG FOCPG TQRPG
mode
Settings
When PG loss, encoder signal error, pulse signal setting error or signal error, if time exceeds
the detection time for PG feedback fault (Pr.10-03), the PG signal error will occur. Refer to the
Pr.10-02 for PG feedback fault treatment.
10-04

ASR (Auto Speed Regulation) control (P) 1

Control
VFPG FOCPG
mode
Settings
10-05

ASR (Auto Speed Regulation) control (I) 1

Control
VFPG FOCPG
mode
Settings
10-06
ASR (Auto Speed Regulation) control (P) 2
Control
VFPG FOCPG
mode
Settings
10-07
ASR (Auto Speed Regulation) control (I) 2
Control
VFPG FOCPG
mode
Settings
10-08
ASR 1/ASR2 Switch Frequency
Control
VFPG FOCPG
mode
Settings
ASR P determines Proportional control and associated gain (P). ASR I determines integral
control and associated gain (I).
Revision August 2008, 03VE, SW V2.04
0
Warn and keep operating
1
Warn and RAMP to stop
2
Warn and COAST to stop
0.00 to 10.00 sec
0 to 40 Hz
0.000 to 10.000 sec
0 to 40Hz
0.000 to 10.000 sec
5.00 o 600.00Hz
Chapter 4 Parameters|
Factory Setting: 2
Factory Setting: 1.00
Factory Setting: 10
Factory Setting: 0.100
Factory Setting: 10
Factory Setting: 0.100
Factory Setting: 7.00
Unit: 0.01
Unit: 0.1
Unit: 0.001
Unit: 0.1
Unit: 0.001
Unit: 0.01
4-151

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents