Group 3 Analog Input/Output Parameters

Pr.
Explanation
Analog Input 1 (AVI)
03-00
Analog Input 2 (ACI)
03-01
Analog Input 3 (AUI)
03-02
Analog Input Bias 1
03-03
(AVI)
Analog Input Bias 2
03-04
(ACI)
Analog Input Bias 3
03-05
(AUI)
Positive/negative Bias
03-06
Mode (AVI)
Positive/negative Bias
03-07
Mode (ACI)
Positive/negative Bias
03-08
Mode (AUI)
Analog Input Gain 1
03-09
(AVI)
Analog Input Gain 2
03-10
(ACI )
Analog Input Gain 3
03-11
(AUI)
ACI/AVI2 Selection
03-12
Analog Input Delay
03-13
Time (AVI)
Analog Input Delay
03-14
Time (ACI)
Analog Input Delay
03-15
Time (AUI)
Addition Function of
03-16
the Analog Input
Loss of the ACI Signal 0: Disable
03-17
Analog Output
03-18
Selection 1
Analog Output
03-21
Selection 2
Analog Output
03-24
Selection 3
Revision August 2008, 03VE, SW V2.04
Settings
0: No function
1: Frequency command (torque limit under TQR control
mode)
2: torque command (torque limit under speed mode)
3: Torque compensation command
4: PID target value (refer to group 8)
5: PID feedback signal (refer to group 8)
6: P.T.C. thermistor input value
7: Positive torque limit
8: Negative torque limit
9: Regenerative torque limit
10: Positive/negative torque limit
11: PID feedback signal of tension
12: Line speed
13: Reel diameter
14: PID target value of tension (tension closed-loop)
15: Tension setting (tension open-loop)
16: Zero-speed tension
17: Tension taper
-100.0~100.0%
-100.0~100.0%
-100.0~100.0%
0: Zero bias
1: Lower than bias=bias
2: Greater than bias=bias
3: The absolute value of the bias voltage while serving
as the center
4: Serve bias as the center
-500.0~500.0%
-500.0~500.0%
-500.0~500.0%
0: ACI
1: AVI 2
0.00~2.00 sec
0.00~2.00 sec
0.00~2.00 sec
0: Disable (AVI, ACI, AUI)
1: Enable
1: Continue operation at the last frequency
2: Decelerate to stop
3: Stop immediately and display E.F.
0: Output frequency (Hz)
1: Frequency command (Hz)
2: Motor speed (Hz)
3: Output current (rms)
4: Output voltage
5: DC Bus Voltage
6: Power factor
7: Power
8: Output torque
Chapter 4 Parameters|
Factory
VF
VFPG SVC
Setting
1
0
0
0
0
0
0
0
0
100.0
100.0
100.0
0
0.01
0.01
0.01
0
0
FOCPG TQRPG
4-9