Analog Output Signal (Afm); Analog Output Gain - Delta Electronics AC Motor Drive VFD-EL User Manual

Vfd-el multiple functions / micro type ac motor drive
Table of Contents

Advertisement

master freq. attained
(output signal)
desired freq. attained
setting 03 zero speed indication
setting 19 zero speed indication
03.03

Analog Output Signal (AFM)

Settings
This parameter sets the function of the AFM output 0~+10VDC (ACM is common).
03.04

Analog Output Gain

Settings
This parameter sets the voltage range of the analog output signal AFM.
When Pr.03.03 is set to 0, the analog output voltage is directly proportional to the output
frequency of the AC motor drive. With Pr.03.04 set to 100%, the Maximum Output Frequency
(Pr.01.00) of the AC motor drive corresponds to +10VDC on the AFM output.
Similarly, if Pr.03.03 is set to 1, the analog output voltage is directly proportional to the output
current of the AC drive. With Pr.03.04 set to 100%, then 2.5 times the rated current
corresponds to +10VDC on the AFM output.
NOTE
Any type of voltmeter can be used. If the meter reads full scale at a voltage less than 10V, Pr.
03.04 should be set using the following formula:
Pr. 03.04 = ((meter full scale voltage)/10) x 100%
Revision August 2008, 2ELE, V1.02
Frequency
master
frequency
detection range
desired
waiting time
frequency
for
03.02
frequency
run/stop
OFF
ON
ON
output timing chart of multiple function terminals
when setting to frequency attained or zero speed indication
0
Analog Frequency Meter (0 to Maximum Output Frequency)
1
Analog Current Meter (0 to 250% of rated AC motor drive current)
1 to 200%
2Hz
ON
OFF
ON
ON
OFF
OFF
Chapter 4 Parameters|
detection
4Hz
range
detection
-2Hz
range
DC braking time
during stop
Time
OFF
OFF
OFF
ON
ON
Factory Setting: 0
Factory Setting: 100
Unit: 1
4-49