Diagnosis and troubleshooting
56
11.2
Diagnostic information on local display
11.2.1
Diagnostic message
Measured value display and diagnostic message in alarm condition
Faults detected by the device' s self-monitoring system are displayed as a diagnostic
message in alternation with the unit.
1
Status signal
2
Status symbol with diagnostic event
Faults detected by the device' s self-monitoring system are displayed as a diagnostic
message in alternation with the measured value display.
1
Status signal
2
Status symbol with diagnostic event
3
Event text
Status signals
F
"Failure (F)" option
A device error has occurred. The measured value is no longer valid.
C
"Function check (C)" option
The device is in the service mode (e.g. during a simulation).
S
"Out of specification (S)" option
The device is being operated:
• Outside of its technical specifications (e.g. during startup or a cleaning)
• Outside of the configuration performed by the user (e.g. level outside configured span)
M
"Maintenance required (M)" option
Maintenance required. The measured value remains valid.
1
X
2
X X X X X X X
X
X
S801
X X X X X X X
X
i
Cerabar PMP71B HART
S
1
2
X
3
Endress+Hauser
A0043759
A0043103