YASKAWA LonWorks SI-W3 Installation Manual page 14

Hide thumbs Also See for LonWorks SI-W3:
Table of Contents

Advertisement

4 Option Components
The operational status of the option LEDs after the power-up diagnostic LED sequence is
complete are described in
A - 1000-Series, Z1000U
B - GA700, GA800
*1
LED label has transparent background and white letters. Please make sure that you use the correct label for
Z1000, HV600, or FP605.
LED Name
Color
RUN
Green
RX
Green
TX
Green
ERR
Red
14
Table
4.2.
Figure 4.2 Option LED Labels
Table 4.2 Option LED States
Indication
Display
ON
No Fault
Network status is not
Flashing
configured
Power supply off
OFF
Hardware fault
ON/Flashing
Receiving
OFF
Node data not yet received No input signal
ON/Flashing
Sending
OFF
Not sending data
ON
Hardware fault
Flashing
Comm error
C - Z1000, HV600, and FP605
Operating State
The option is operating normally.
You have not configured the
LonWorks network.
Power is not being supplied to the
drive.
The option detected a fatal
(unrecoverable) error.
If the unit does not recover after you
cycle power, you may need to replace
the option.
Receiving node data
Sending data
No data is being sent
The option detected a fatal
(unrecoverable) error.
If the unit does not recover after you
cycle power, you may need to replace
the option.
The option detected a CALL or bUS
error.
YASKAWA TOEP C730600 93B LonWorks Installation Manual