Network Variables

Drive and Network Variables

Figure 7.1
outlines the relationship between drive and network variables.
YASKAWA TOEP C730600 93B LonWorks Installation Manual
Description
When you enable this parameter, d5-01 [Torque
Control Selection] sets the drive to read the value as the
Torque Limit value or the Torque Reference value.
d5-01 = 0: Torque Limit
d5-01 = 1: Torque Reference
When A1-02 = 2, 8 [Control Method Selection = Open
Loop Vector, EZ Vector Control], the drive reads this
value as the Torque Limit.
–HV600, FP605
Parameter is available in A1-02 = 8 [Control Method
Selection = EZ Vector Control].
When A1-02 = 8 [Method Selection = EZ Vector
Control], the drive reads this value as the Torque Limit.
• If the PLC does not supply a torque reference or torque
limit when F6-06 = 1 [Torque Reference/Limit by Comm
= Enabled], the motor cannot rotate.
0 : MultiStep References Disabled
1 : MultiStep References Enabled
Selects whether communication-related parameters F6-xx and
F7-xx are set back to original default values when you use
parameter A1-03 [Initialize Parameters] to initialize the drive.
0 : No Reset - Parameters Retained
1 : Reset - Back to Factory Default
Note:
When you set F6-08 to 1 and you then use A1-03 to
initialize the drive, the drive will not change this setting
value.
7 Network Variables
Default
(Range)
0
(0, 1)
0
(0, 1)
47