Items
Model
Node Type
Communication Speed
Communication IC
Communication Driver
Communication Protocol
Network Variable
Network Variable Alias
Maximum Number of
Connections
Total Wiring Length
Ambient Temperature
Humidity
Storage Temperature
Area of Use
Altitude
62
Table 11.1 Option Specifications
SI-W3
Host Application Node
78 kbps
Neuron chip FT3120
FT-X1 (free topology)
LonTalk protocol node
Total: 236
Standard Network Variable Types (SNVT): Variable Speed Motor Drive
function profile Ver1.1
Maximum: 50
64 (in one segment)
Max 500 m
-10°C - +50°C (14°F - 122°F)
Up to 95% RH (no condensation)
-20°C - +60°C (-4°F - 140°F) allowed for short-term transport of the product
Indoors and free from:
• Oil mist, corrosive gas, flammable gas, and dust
• Radioactive materials or flammable materials, including wood
• Harmful gas or fluids
• Salt
• Direct sunlight
• Falling foreign objects
Up to 1000 m (3280 ft)