6 Installation
6-2

Control Panel Installation

To ensure system reliability and safety, the system must be designed and configured according to the
installation environment (temperature, humidity, vibration, shock, corrosive gases, overcurrent, noise,
etc.).
6-2-1

Temperature

Panels have been reduced in size due to space-saving and miniaturization in devices and systems, and
the temperature inside the panel may be at least 10 to 15°C higher than outside the panel. Implement
the following measures against overheating at the installation site and in the panel, and allow a suffi-
cient margin for the temperature.
High Temperatures
Use the following cooling methods as required, taking into account the ambient temperature and the
amount of heating inside the panel.
 Natural Cooling
Natural cooling relies on natural ventilation through slits in the panel, rather than using cooling
devices such as fans or coolers.
When using this method, observe the following points.
• Do not install the EtherNet/IP Slave Terminal at the top of the panel, where hot air tends to stag-
nate.
• To provide ventilation space above and below the EtherNet/IP Slave Terminal, leave sufficient dis-
tance from other devices, wiring ducts, etc.
• Do not install the EtherNet/IP Slave Terminal directly above heat-generating equipment, such as
heaters, transformers, and devices with high resistance.
• Do not install the EtherNet/IP Slave Terminal in a location exposed to direct sunlight.
Natural Cooling
6 - 24
EtherNet/IP
Slave
Terminal
EtherNet/IP
Slave
Terminal
NX-series EtherNet/IP Coupler Unit User's Manual (W536)