Cautions - Omron NXEIP202 User Manual

Machine automation controller
Table of Contents

Advertisement

Voltage and Current Inputs
Make sure that the voltages and currents that are input to the Units and slaves are within
the specified ranges.
Inputting voltages or currents that are outside of the specified ranges may cause accidents
or fire.
Transferring
Always confirm safety at the destination node before you transfer Unit configuration infor-
mation, parameters, settings, or other data from tools such as the Sysmac Studio.
The devices or machines may operate unexpectedly, regardless of the operating mode of
the Controller.

Cautions

Wiring
When you connect a computer or other peripheral device to a Communications Coupler
Unit that has a non-isolated DC power supply, either ground the 0-V side of the external
power supply (i.e. Unit power supply) or do not ground it at all.
If the peripheral devices are grounded incorrectly, the external power supply (i.e. Unit
power supply) may be short-circuited.
Never ground the 24-V side of the power supply, as shown in the following figure.
Peripheral device
(e.g., computer)
Be sure that all terminal screws and cable connector screws are tightened to the torque
specified in the relevant manuals. The loose screws may result in fire or malfunction.
NX-series EtherNet/IP Coupler Unit User's Manual (W536)
Caution
Communications Coupler Unit
Non-isolated DC power
supply (internal power
supply circuit)
Peripheral device
cable
Safety Precautions
NX Unit power
supply
24 V
0 V
Ground terminal
Unit power
supply
17

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nx series

Table of Contents