12 Troubleshooting
Event name
Link OFF Detected
Meaning
Disconnection of an Ethernet link was detected.
Source
EtherNet/IP
Error
Level
attributes
Effects
User program
Sys-
Variable
tem-defined
None
variables
Cause and
Assumed cause
correction
An Ethernet cable is broken, dis-
connected, or loose.
The Ethernet switch power supply
is turned OFF.
Link speed mismatch.
Noise
Attached
None
information
Precautions/
None
Remarks
12 - 46
Source details
Observation
Recovery
Continues.
Operation
Data type
---
Correction
Connect the Ethernet cable
securely. If the cable is broken,
replace it.
Turn ON the power supply to the
Ethernet switch. Replace the
Ethernet switch if it fails.
Make the port settings at the
remote node to the auto negotia-
tion setting.
Implement noise countermea-
sures if there is excessive noise.
Event code
84540000 hex
EtherNet/IP
Detection
Coupler Unit
timing
Reset error in
Log category
EtherNet/IP
Coupler Unit.
Not affected.
Name
---
Prevention
Connect the Ethernet cable
securely. Check the cable to make
sure that it is not disconnected.
Do not turn OFF the power supply
to the Ethernet switch.
Make the port settings at the
remote node to the auto negotia-
tion setting.
Implement noise countermea-
sures.
NX-series EtherNet/IP Coupler Unit User's Manual (W536)
After link is
established
System