Omron NXEIP202 User Manual page 396

Machine automation controller
Table of Contents

Advertisement

Appendices
Step
4
Write the values to the NX object
in the NX Unit with unit number 2.
:
5
Write the values to the NX object
in the NX Unit with unit number
63.
6
Save the set values in the Ether-
Net/IP Coupler Unit.
7
Save the set values in the NX Unit
with unit number 1.
8
Save the set values in the NX Unit
with unit number 2.
:
9
Save the set values in the NX Unit
with unit number 63.
10
Restart the Slave Terminal.
If tag data link communications
*1
11
are set in the EtherNet/IP master,
the tag data links will recover auto-
*2
matically.
Write the initial values of the out-
*3
11
put data to the Units in the Ether-
Net/IP Slave Terminal.
Change the Units in the Ether-
*3
12
Net/IP Slave Terminal to the Oper-
ational state.
*1. This process occurs when you use an EtherNet/IP master that supports explicit messages.
*2. If tag data link communications are not set in the EtherNet/IP master, refer to A-3-6 Reading and Writing I/O
Data for EtherNet/IP Slave Terminals A-49 on page A-1 for the method to restart I/O communications.
*3. This process is not necessary when you use an EtherNet/IP master that supports explicit messages.
*4. This is necessary to prevent invalid data from being output as soon as the Units in the EtherNet/IP Slave Ter-
minal enter the Operational state.
A - 48
Description
0x74
NX Configuration
object
:
0x74
NX Configuration
object
0x74
NX Configuration
object
0x74
NX Configuration
object
0x74
NX Configuration
object
:
0x74
NX Configuration
object
0x01
Identity object
---
0x04
Assembly object
*4
0x74
NX Configuration
object
CIP objects to use
Class ID
Instance ID
0x01
:
:
0x01
0x01
0x01
0x01
:
:
0x01
0x01
---
0x94
0x01
NX-series EtherNet/IP Coupler Unit User's Manual (W536)
Unit
Service code
number
0x34
0x02
Write NX object
:
:
0x34
0x3F
Write NX object
0x36
0x00
Save parameter
0x36
0x01
Save parameter
0x36
0x02
Save parameter
:
:
0x36
0x3F
Save parameter
0x05
Setting
not
Reset
required.
---
---
0x10
Setting
not
Set_Attribute
required.
_Single
0x39
0x00
Change NX state

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nx series

Table of Contents