6 Installation
 Calculation Example for the Configuration Width of an EtherNet/IP Slave Ter-
minal
NX Units: Digital Input Units
with 4 inputs each
EtherNet/IP Coupler Unit
The widths of the Units in the example EtherNet/IP Slave Terminal configuration and the total config-
uration width are given below.
EtherNet/IP Coupler Unit
NX Units: Digital Input Units
NX Units: Temperature Input Units
End Cover
Total:
Additional Information
You can check the width of a Slave Terminal when you create the Unit configuration on the Edit
Slave Terminal Configuration Tab Page on the Support Software. You can display the width on
the right of the Slave Terminal on Edit Slave Terminal Configuration Tab Page on the Support
Software. Click
6 - 22
NX Units:
Temperature Input Units
with 4 inputs each
Name
to display the width.
End Cover
Model
NX-EIC202
NX-ID3317
NX-TS3101
NX-END01
W = 46 + (12 × 4) + (24 × 2) + 12 = 154 mm
NX-series EtherNet/IP Coupler Unit User's Manual (W536)
Unit width
46 mm
12 mm × 4 Units
24 mm × 2 Units
12 mm