10 I/O Refreshing
 Minimum I/O Response Time
The minimum I/O response time (T
T
= T
+ T
min
in
PLC
EtherNet/IP
EtherNet/IP
Coupler Unit
NX Input Unit
T
in
NX Output Unit
T
: NX Input Unit switching response time
in
T
: NX bus communication time = 1.5 ms
nxb_cycle
T
: EtherNet/IP Coupler's communication time (input)
rt_in
T
: PLC cycle time
plc
T
: EtherNet/IP Coupler's communication time (output)
rt_out
T
: NX bus communication time = 1.5 ms
nxb_cycle
T
: NX Output Unit switching response time
out
10 - 6
) can be calculated with the following formula.
min
+ T
+ T
+ T
nxb_cycle
rt_in
plc
rt_out
T
rt_in
T
= 1.5 ms
nxb_cycle
+ T
+ T
nxb_cycle
out
T
min
T
plc
T
rt_out
T
= 1.5 ms
nxb_cycle
NX-series EtherNet/IP Coupler Unit User's Manual (W536)
T
out