12 Troubleshooting
Event name
IP Address Duplication Error
Meaning
The same IP address is used more than once
Source
EtherNet/IP
Error
Level
attributes
Effects
User program
Sys-
Variable
tem-defined
None
variables
Cause and
Assumed cause
correction
The IP address of the EtherNet/IP
port is also used as the IP address
of another node
Attached
Attached information 1: Duplicated IP address (example: C0A8FA01 hex = address 192.168.250.1)
information
Precautions/
When the EtherNet/IP Coupler Unit is started or the link of the EtherNet/IP port is established, an ARP
Remarks
request is broadcasted with the set IP address. A duplicated address error occurs if there is an ARP
response from another node for this request.
12 - 38
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Perform either of the following and
then cycle the power supply to the
EtherNet/IP Coupler Unit or restart
the EtherNet/IP Coupler Unit.
• Check the IP addresses of other
nodes and correct the IP
address settings so that the
same address is not used by
more than one node.
• Remove the node that has the
duplicate IP address from the
network.
Event code
84500000 hex
EtherNet/IP
Detection
Coupler Unit
timing
Cycle power to
Log category
the EtherNet/IP
Coupler Unit or
restart the
Slave Terminal.
When Fail-soft Operation Is Set to Fail-soft
• EtherNet/IP Coupler Unit, EtherNet/IP Communi-
cations
Ethernet communication stops.
• NX Bus
(1) NX Safety Standalone mode
I/O refreshing to the NX Units continues.
(2) Remote I/O mode.
I/O refreshing to the NX Units stops.
Messages cannot be sent to the NX Units in the
Slave Terminal.
When Fail-soft Operation Is Set to Stop
• EtherNet/IP Coupler Unit, EtherNet/IP Communi-
cations
Ethernet communication stops.
• NX Bus
(1) NX Safety Standalone mode
I/O refreshing to the NX Units stops.
(2) Remote I/O mode.
I/O refreshing to the NX Units stops.
Messages cannot be sent to the NX Units in the
Slave Terminal.
Name
---
Prevention
Set the IP address of the Ether-
Net/IP Coupler Unit so that the
same address is not used by
another node.
NX-series EtherNet/IP Coupler Unit User's Manual (W536)