Control Panel Installation

To ensure system reliability and safety, the system must be designed and configured according to the
installation environment (temperature, humidity, vibration, shock, corrosive gases, overcurrent, noise,
etc.).
4-5-1

Temperature

Panels have been reduced in size due to space-saving and miniaturization in devices and systems, and
the temperature inside the panel may be at least 10 to 15°C higher than outside the panel. Implement
the following measures against overheating at the installation site and in the panel, and allow a suffi-
cient margin for the temperature.
High Temperatures
Use the following cooling methods as required, taking into account the ambient temperature and the
amount of heating inside the panel.
 Natural Cooling
• Natural cooling relies on natural ventilation through slits in the panel, rather than using cooling
devices such as fans or coolers. When using this method, observe the following points.
• Do not install the Controller at the top of the panel, where hot air tends to stagnate.
• To provide ventilation space above and below the Controller, leave sufficient distance from other
devices, wiring ducts, etc.
• Do not mount the Units in the wrong direction (e.g., vertically or upside down). Doing so may
cause abnormal heating in the Controller.
• Do not install the Controller directly above any heat-generating equipment, such as heaters,
transformers, and devices with high resistance.
• Do not install the Controller in a location exposed to direct sunlight.
Natural Cooling
NX-series CPU Unit Hardware User's Manual (W535)
Controller
Controller
4 Installation and Wiring
4
4 - 39