SmartServo ports, the FW/HD LED shows green
3. Bottom Three Status LEDs
NOTE: The Bottom Status LEDs have different meanings when the SmartController is
used with ePLC Connect software. Refer the the Adept ePLC Connect User's Guide, chapt-
ger 3, for a description of those LEDs with ePLC Connect.
The bottom three LEDs on the front of the Adept SmartController EX motion controller
give the following information about the status of the main controller.
O = Off
G = Green
LED Display
1 2 3
O-O-O
0
R-O-O
1
O-R-O
2
O-O-R
4
O-R-R
6
R-R-R
7
G-O-O
9
O-O-G
C
G-O-G
D
If the Adept SmartController EX motion controller displays an error, cycle the
power off, then on again. If the problem persists, contact Adept Customer Service.
4. SW1 DIP switches
The definition for DIP switches on the Adept SmartController EX motion controller is as
follow:
Switch 1:
OFF: use IP address from configuration on SD card
l
ON: use default factory IP address (printed on the bottom of the controller)
l
Switch 2:
OFF: normal connection through Ethernet
l
ON: communication through RS-232 on the TERM port
l
Adept SmartController EX User's Guide, Rev.C
Chapter 3: Operation
R = Red
Table 3-2. LED Status Indicators
Error
Description
Number
No error.
System clock is dead or too fast. Clock inter-
rupts are not being received.
Hardware configuration error.
Memory test failure. Free storage error.
Software serial I/O configuration error.
Initial display set by hardware before software
has started.
Transient display set when PCI is configured.
Uninitialized trap.
Bus error detected.