Select the slave unit(s) you want to configure one after the other and configure the de-
tection capability, the zones and the reference outlines, as required.
17. Switch the display in the work window to a live image by clicking on
Check the safety function of the safety laser scanner as indicated in
Inspection [
Each time the test piece enters into the safety zone, the OSSDs must switch to the OFF
state and the status of the OSSDs in the Monitoring work window must show the viola-
tion of the safety zone.
The OSSDs must switch to the OFF state each time the reference point changes bey-
ond the tolerance range, and the status of the OSSDs in the Monitoring work window
must show the changing of the reference points.
18. Select Download configuration to device, to transfer the configuration to the device.
Click Accept to activate the downloaded configuration in the connected device and re-
ject the existing configuration on the connected device.
Save the report in PDF format.
Click Reject to reject the downloaded configuration in the connected device and con-
tinue to use the existing configuration on the connected device. The downloaded con-
figuration in the connected device will be deleted.
9.4

Testing

Before finally commissioning the safety laser scanner after the installation and alignment, fi-
nal inspections must be carried out.
Check safety function of the safety laser scanner
Procedure:
As a test piece, use an opaque object with a height of at least 300 mm and a diameter that
corresponds to the selected detection capability.
Move the test piece at various points along the safety zone into the safety zone:
The OSSDs must switch to the OFF state with each entry of the test piece.
Supplementary test step for vertical applications
Change the position of the reference points beyond the tolerance range of the reference
points:
The OSSDs must switch to the OFF state with each change of the reference point beyond
the tolerance range.
Operating Manual PSEN sc M 3.0/5.5 08-12
1005055-EN-03
85].
INFORMATION
This inspection may only be carried out by qualified personnel.
.