Muting In One Direction - Pilz PSEN sc M 3.0 08-12 Operating Manual

Hide thumbs Also See for PSEN sc M 3.0 08-12:
Table of Contents

Advertisement

Project configuration
5.14.3

Muting in one direction

}
The muting status occurs
– When the signal at the muting input 2 switches to High after the muting input 1 has
– The delay between the two signal changes is in the configurable area Muting activa-
}
The muting state is ended
– When the configured time is reached or
– after a multiple of the delay between the activation of the two muting sensors.
Fig.: Timing diagram L muting
Legend
Operating Manual PSEN sc M 3.0/5.5 08-12
1005055-EN-03
DANGER!
Loss of the safety function when L muting is applied incorrectly.
– Use L muting only to remove material from the danger zone.
also switched to high (or the muting input 1 switches to High after the muting input 2)
and
tion delay [ms]. The max. delay can be configured between 1 and 16 seconds.
The Factor activation delay can be selected between 2 and 16.
Input
At
Muting 1
Off
At
Input
Muting 2
Off
At
Muting
function
Off
t
Delay between Muting 1 and Muting 2 (configurable from 1-16 s)
1
t
Duration of the muting state (max. up to the configurable time exceeded)
2
t
Internal delay before the ending of the muting state (max. 30 ms)
3
t
2
t
t
1
3
t