Activate Rest Condition; Deactivate Rest Condition - Pilz PSEN sc M 3.0 08-12 Operating Manual

Hide thumbs Also See for PSEN sc M 3.0 08-12:
Table of Contents

Advertisement

Operation
Procedure:
Hold the reset pushbutton down for at least 500 ms.
10.7

Activate rest condition

Prerequisites
}
At least two zone sets are configured.
}
No safety or warning zones are configured in the relevant zone set.
Procedure:
1. Select the Configure zone sets window.
Select Rest condition = Activated.
2. The display of the safety laser scanner shows for 30 seconds that the rest condition is
started.
Then the display switches to the energy saving mode and the LEDs will go out.
Remove device from the arrangement of safety laser scanners
When removing a device from an arrangement of safety laser scanners while this arrange-
ment is in a rest condition, an error message INTF18 is displayed when switching on the ar-
rangement.
Switch off the arrangement again, deactivate the rest condition in the configuration and
switch the arrangement on again.
The master unit displays the error INTF18, the slave units are in normal operation.
Now change the structure of the arrangement of safety laser scanners.
10.8

Deactivate rest condition

Procedure:
1. Select the Configure zone sets window.
Select Rest condition = Deactivated.
2. After approx. 30 seconds the safety laser scanner is again in normal operation.
The display and the LEDs of the safety laser scanner show normal operation.
Operating Manual PSEN sc M 3.0/5.5 08-12
1005055-EN-03
| 96