Figure 23: Configuring Digital Inputs 5; Table 26: Configuring Of Digital Inputs - WAGO -TO-PASS 761 Manual

To-pass mobile, 4 ai telecontrol module for fault detection/indication, position monitoring and remote control
Hide thumbs Also See for WAGO-TO-PASS 761:
Table of Contents

Advertisement

54
Parameterizing
Figure 23: Configuring digital inputs 5 ... 8 (when provided)

Table 26: Configuring of digital inputs

Counters (only for digital inputs 1 ... 4)
Counters
Starting value
End value
Check this box to use the selected digital input as a counter
input.
To activate the counter click the button [Activate]. This
button is only active when the input is used as a counter
input. On completion of configuration, the counter can be
activated/deactivated during operation via the visualization
system.
This function is available starting with Firmware Version FW
2.33.
In this field enter the starting value for the counter.
This field is only active when the input is used as a counter
input.
In this field enter the end value for the counter.
This field is only active when the input is used as a counter
input.
If the starting value is less than the end value the counter will
count upward. If the end value is exceeded, the counting
process is restarted from the starting value.
If the starting value is greater than the end value the counter
will count downward. If counting then continues below the
end value, the counting process is restarted from the starting
value.
WAGO-TO-PASS® 761
761-314 TO-PASS® Mobile, 4 AI
Version 2.0.0
Manual