  • Page 1 SmartACU2000D Smart Array Controller User Manual (With PID Modules) Issue Date 2023-09-26 HUAWEI TECHNOLOGIES CO., LTD.
  • Page 2 Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
  • Page 3: About This Document

    About This Document About This Document Purpose This document describes the SmartACU2000D Smart Array Controller (SACU for short), which is an outdoor cabinet, in terms of its installation, electrical connections, commissioning, and maintenance. Before installing and operating an SACU, read this manual carefully to get familiar with the functions and features of the device as well as the precautions.
  • Page 4 4.2 Unpacking and Acceptance. Updated 4.3 Preparing Tools. Issue 02 (2020-08-18) Added A Scenario Where a Longitudinal Encryption Device Is Used. Issue 01 (2020-02-14) This issue is used for first office application (FOA). Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 5: Table Of Contents

    4.6.1 Opening the Main Cabinet Door..........................45 4.6.2 (Optional) Installing the SmartModule........................46 4.6.3 (Optional) Installing the Ethernet Switch.........................47 4.6.4 (Optional) Installing the 24 V Power Module......................49 4.6.5 Installing the PoE Module.............................. 50 Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 6 7.3.10 Replacing the PID Module Switch..........................95 7.3.11 Replacing the Fiber Adapter............................95 7.3.12 Replacing the USB Port..............................96 8 Technical Specifications....................... 97 A Scenario Where a Longitudinal Encryption Device Is Used........99 Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 7 SmartACU2000D Smart Array Controller User Manual (With PID Modules) Contents B Acronyms and Abbreviations................... 102 Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 8: Safety Information

    The equipment is damaged due to force majeure such as earthquakes, floods, volcanic eruptions, debris flows, lightning strikes, fires, wars, armed conflicts, typhoons, hurricanes, tornadoes, and other extreme weather conditions. ● The equipment is operated beyond the conditions specified in this document. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 9: Personal Safety

    D ANGER During operations, use dedicated insulated tools to prevent electric shocks or short circuits. The dielectric withstanding voltage level must comply with local laws, regulations, standards, and specifications. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 10 Professionals: personnel who are familiar with the working principles and structure of the equipment, trained or experienced in equipment operations and are clear of the sources and degree of various potential hazards in equipment installation, operation, maintenance Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 11: Mechanical Safety

    Otherwise, tipping or falling cabinets may cause bodily injury and equipment damage. WARNING When pulling equipment out of a cabinet, be aware of unstable or heavy objects in the cabinet to prevent injury. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 12 ● Move a heavy object stably with balanced force at an even and low speed. Put down the object stably and slowly to prevent any collision or drop from Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 13 ● Before using a ladder, check that it is intact and confirm its load bearing capacity. Do not overload it. ● Ensure that the ladder is securely positioned and held firm. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 14 Do not drag steel ropes and hoisting tools or bump the hoisted objects against hard objects during hoisting. ● Ensure that the angle between two hoisting ropes is no more than 90 degrees, as shown in the following figure. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 15: Electrical Safety

    General Requirements ● Follow the procedures described in the document for installation, operation, and maintenance. Do not reconstruct or alter the equipment, add components, or change the installation sequence without permission. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 16 Ensure that the grounding impedance of the equipment complies with local electrical standards. ● Ensure that the equipment is connected permanently to the protective ground. Before operating the equipment, check its electrical connection to ensure that it is reliably grounded. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 17 Do not perform any improper operations, for example, dropping cables directly from a vehicle. Otherwise, the cable performance may deteriorate due to cable damage, which affects the current-carrying capacity and temperature rise. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 18: Environment Requirements

    Do not install, use, or operate outdoor equipment and cables (including but not limited to moving equipment, operating equipment and cables, inserting connectors to or removing connectors from signal ports connected to outdoor facilities, working at heights, performing outdoor installation, and opening Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 19 All cable holes must be sealed. Seal the used cable holes with sealing putty. Seal the unused cable holes with the caps delivered with the equipment. The following figure shows the criteria for correct sealing with sealing putty. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 20 SmartACU2000D Smart Array Controller User Manual (With PID Modules) 1 Safety Information ● After installing the equipment, remove the packing materials such as cartons, foam, plastics, and cable ties from the equipment area. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 21: Overview

    D: ≤ 800 V three-phase AC input Configuration ● 01: one MBUS route and one SmartPID2000 (referred to as PID module hereinafter) ● 03: two MBUS routes and two PID modules Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 22 User Manual (With PID Modules) 2 Overview Model Identification You can view the SACU model on its nameplate. Figure 2-2 Nameplate (SmartACU2000D-D-03 as an example) (1) Trademark and model (2) Key technical specifications (3) Compliance symbols (4) Company name and country of origin NO TE The nameplate figure is for reference only.
  • Page 23: Product Introduction

    ● Easy to use: Supports wizard-based settings, facilitating parameter settings and device connection. ● Stable and reliable: Has a built-in surge protection module for safe and reliable industrial applications. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 24 RSTP and bridge priority of the switch, contact the vendor. If the switch does not support the RSTP, the fiber ring topology must be changed to a chain or star topology. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 25: Appearance

    Figure 2-3 Appearance of the product Component Description PID cabinet door The PID cabinet is only for PID modules. Do not install third- party devices in the cabinet. Main cabinet door Hanging kit Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 26 (including the (0.71–0.98 in.) functional earthing wire) (MBUS01/PID01, MBUS02/ PID02) Waterproof connector for the ● Specifications: 3/4 in. single-phase AC power cable ● Inner diameter: 13–18 mm (AC INPUT) (0.51–0.71 in.) Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 27: Enclosure Signs

    Warning label for multiple This device has more than one power inputs power input. Before maintenance, ensure that the upstream switch is OFF. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 28: Product Composition

    2.4 Product Composition NO TE For simplicity purposes, the following figure shows only the components that you need to operate and reserved installation positions. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 29 ● The 24 V DC power module is optional. Its installation position is reserved in the cabinet. PID01 input switch AC: 1 A/3P (QF01) PID02 input switch AC: 1 A/3P (QF02) Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 30 25 A/3P 1 (FU01) RS485 communications 12P; supports the wires with a cross- terminal (JX01) sectional area of 1–2.5 mm (or 18–14 AWG). SmartPID module (PID02) SmartPID2000 SmartPID module (PID01) SmartPID2000 Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 31 Table 2-3 Components and reserved installation positions Name Specifications Quantity PID FE bar (FE01, FE02) SmartLogger power ● AC input: 100–240 V, 50 Hz/60 Hz adapter (U01) ● DC output: 12 V/2 A Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 32 TX1 RX1; OFA02: TX2 RX2) Position for the SPD of the power over Ethernet (PoE) module Position for the PoE module (POE) Single-phase input switch 32A/2P (QF03) Three-phase input switch 25A/3P (FU01) Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 33: Working Principles

    WebUI of the SmartLogger3000, choose Monitoring > MBUS > Network Settings, and set Networking to Enable (default value). When the SACU communicates with the inverters SmartLogger3000 User over RS485, set Networking to Disable. For details, see the Manual . ● RS485 communication mode Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 34 PID module, MBUS CCO module, and other devices that support RS485 communication over COM ports. NO TE ● The SmartModule is installed before delivery only for the SmartACU2000D- D-03. ● The figure displays only major components and cables, and is for reference only.
  • Page 35 CCO module connects to the inverters that support MBUS communication over the three-phase AC power cable. NO TE ● The MBUS CCO is installed before delivery only for the SmartACU2000D- D-03. ● The figure displays only major components and cables, and is for reference only.
  • Page 36: Configuration In Different Scenarios

    If a double-winding transformer is used, use the SACU with one PID module. ● If a double-split transformer is used, use the SACU with two PID modules. 2.6 Configuration in Different Scenarios Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 37: Fiber Ring Network

    ● Components in dashed-line boxes are optional. To highlight the key points, the figure does not show all factory-installed components and cables. ● The SmartModule is installed on the SmartACU2000D-D-03 before delivery, and you do not need to perform any operations on the SmartModule. If the SmartACU2000D-D-01 needs to provide more RS485 ports, the SmartModule can be installed.
  • Page 38 (FC) switch. NO TE ● Components listed in the table need to be installed onsite. ● Models of the components inside the transformer station are specified by the transformer station vendor. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 39 V DC output armored copper cable ● 14–12 AWG (14 AWG) power cable ● Connection through a pipe: single-core outdoor copper cable ● Operating voltage to the ground ≥ 300 V Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 40: Lte

    ● Components in dashed-line boxes are optional. To highlight the key points, the figure does not show all factory-installed components and cables. ● The SmartModule is installed on the SmartACU2000D-D-03 before delivery, and you do not need to perform any operations on the SmartModule. If the SmartACU2000D-D-01 needs to provide more RS485 ports, the SmartModule can be installed.
  • Page 41 Note a: If the CPE model is EG860, a PoE SPD is required. NO TE ● Components listed in the table need to be installed onsite. ● Models of the components inside the transformer station are specified by the transformer station vendor. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 42 ● 10–6 AWG (6 AWG) Network cable 20 m (65.62 ft) long network cable from the PoE delivered with the Huawei CPE. If the module or PoE cable is not long enough, prepare a Cat SPD to the CPE 5e outdoor shielded network cable with an outer diameter of less than 9 mm (0.35 in.) and internal resistance of less...
  • Page 43 DC output power outdoor armored copper cable ● 14–12 AWG (14 AWG) cable ● Connection through a pipe: single- core outdoor copper cable ● Operating voltage to the ground ≥ 300 V Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 44: Storage Requirements

    If the SACU has been stored for a long time, it needs to be inspected by professionals before it is put into use. The Company shall not be liable for any consequence caused by violation of the storage requirements specified in this document. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 45: System Installation

    Move the equipment with caution to avoid bumping or falling, which may damage the equipment. ● After placing the equipment in the installation position, unpack it with care to prevent scratches. Keep the equipment stable during unpacking. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 46: Preparing Tools

    Open end: 32 mm Rubber mallet Crimping tool Cable cutter Utility knife RJ45 crimping tool Network cable SPD extracting Multimeter tester tool Heat shrink tubing Heat gun Vacuum cleaner Marker Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 47 4 System Installation Category Tool Level Cable tie Steel measuring Adjustable torque tape wrench Personal protective equipment (PPE) Insulated gloves Protective gloves Goggles Dust mask Safety helmet Reflective vest Insulated shoes Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 48: Installation Requirements

    A mounting bracket has four groups of tapped holes, each group containing four tapped holes. Mark any hole in each group based on site requirements and mark four holes in total. Two round holes are preferred to secure the mounting bracket. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 49 Otherwise, the mounting bracket will not be securely installed on the wall. Step 1 Prepare expansion bolts (M12x60 stainless steel expansion bolts are recommended). Step 2 Install a mounting bracket. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 50 M12 bolt assemblies by yourself and use them together with the supplied M12 nuts.) Step 2 Install a mounting bracket. Figure 4-4 Installing a mounting bracket Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 51: Mounting The Cabinet

    Figures provided in this section are for reference only. The actual poles and pole-mounting brackets may vary. ----End 4.5.2 Mounting the Cabinet Step 1 Lift the cabinet, mount it onto the mounting bracket, and secure it using security Torx screws. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 52: Installing The Components

    ● Do not leave unused screws in the cabinet. Loosen the screws on the main cabinet door, open the cabinet door, and adjust the support bar. Figure 4-7 Opening a cabinet door Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 53: Optional) Installing The Smartmodule

    Step 6 Connect the preinstalled RS485 cable to the COM port on the SmartModule based on the label. Step 7 Connect the preinstalled power cable to the 12V 1A port on the SmartModule based on the cable label. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 54: Optional) Installing The Ethernet Switch

    4.6.3 (Optional) Installing the Ethernet Switch Step 1 Remove the panel behind which an Ethernet switch will be installed. Step 2 Secure the Ethernet switch. Step 3 Connect a PE cable to the Ethernet switch. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 55 Step 4 Connect the FE1 port on the Ethernet switch to the WAN port on the SmartLogger using the network cable delivered with the Ethernet switch. Step 5 Connect the preinstalled power cable to the power port on the Ethernet switch based on the label. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 56: Optional) Installing The 24 V Power Module

    Step 4 Install the 24 V power module in the cabinet. Step 5 Connect the AC input power cables (delivered with the SACU) to the 24 V power module based on the cable label. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 57: Installing The Poe Module

    Step 3 Place the PoE module at the installation position and align the mounting holes. Then secure the PoE module. NO TE Indicators should be in the lower left corner. Step 4 Secure the mounting board. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 58: Optional) Installing The Poe Spd

    Step 4 Place the PoE SPD in the mounting bracket. Ensure that the PE point faces upwards and the surface marked PE faces outwards. Step 5 Secure the PoE SPD fastener. Step 6 Connect the other end of the ground cable to the PE bar. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 59 SmartACU2000D Smart Array Controller User Manual (With PID Modules) 4 System Installation Figure 4-14 Installing a PoE SPD ----End Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 60: Electrical Connections

    ● The cable colors shown in the electrical connection diagrams provided in this chapter are for reference only. Select cables in accordance with local cable specifications (green-and-yellow cables are only used for protective earthing). Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 61: Selecting A Connection Mode

    Step 5 Clear foreign matter from the cabinet. ----End 5.1.2 Connection Through a Pipe If you choose connection through a pipe, ensure that an appropriate cable and a pipe are available. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 62 Step 2 Secure the pipe fitting using the nut delivered with the pipe. Figure 5-3 Installing a pipe fitting Step 3 Route the cable through the pipe conduit and then the fitting, and connect the cable. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 63: Crimping The Ot Terminal

    ● Wrap the wire crimping area with heat shrink tubing or insulation tape. The heat shrink tubing is used as an example. ● Use a heat gun carefully to avoid heat damage to the equipment. Figure 5-4 Crimping an OT terminal Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 64: Connecting The Pe Cable

    SFP2 port faces downwards. ● If you hear a click when inserting the optical module, the optical module snaps into place. Then pull it back to ensure that it is secure. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 65 ● Only professionals are allowed to connect and splice optical cables. NO TE Connect two optical cables in a fiber ring network, and connect one optical cable in a star optical network. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 66 5 Electrical Connections Figure 5-7 ATB interior (1) Fiber spool (2) Fixing points for internal (3) Cable clip steel wires of optical cables Step 1 Remove the external mechanical parts from the ATB. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 67 SmartACU2000D Smart Array Controller User Manual (With PID Modules) 5 Electrical Connections Figure 5-8 Removing external mechanical parts Step 2 Remove the optical cable fastener. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 68 Step 5 Connect the peripheral optical cable to the ATB, splice the optical cable and the optical jumper, and then wind the spliced cable around the fiber spool on the ATB. NO TICE Only professionals are allowed to splice fibers. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 69: Connecting The 4G Lte Cable (With A Poe Spd)

    5.5 Connecting the 4G LTE Cable (With a PoE SPD) Step 1 Connect the POE port on the PoE module to the PROTECT port on the PoE SPD using the network cable delivered with the PoE SPD. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 70 Step 2 Connect the factory-installed network cable on the SmartLogger to the DATA port on the PoE module. Step 3 Connect the factory-installed power cable on the SmartLogger to the PoE module. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 71 User Manual (With PID Modules) 5 Electrical Connections Figure 5-12 Connecting cables to a PoE module Step 4 Connect the network cable delivered with the CPE to the Surge port on the PoE SPD. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 72: Connecting The 4G Lte Cable (Without A Poe Spd)

    Step 1 Connect the factory-installed network cable on the SmartLogger to the DATA port on the PoE module. Step 2 Connect the factory-installed power cables on the SmartLogger to the PoE module. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 73 User Manual (With PID Modules) 5 Electrical Connections Figure 5-14 Connecting cables to a PoE module Step 3 Connect the network cable delivered with the CPE to the POE port on the PoE module. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 74: Connecting The Three-Phase Ac Power Cable

    SACU with two PID modules. For details about the single PID module situation, refer to the way of connecting the first route of three-phase AC power cable. Step 1 Prepare a cable. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 75 ● Ensure that the L1, L2, and L3 cables are connected in correct phase sequence. ● Do not mix up the cables to the FE01 port with the cables to the FE02 port. Step 4 Bind the cable. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 76: Connecting The Peripheral Rs485 Communications Cables

    RS485 communications cables. Table 5-1 Definition of the JX01 terminal block Port on the JX01 Definition Terminal Block RS485-1 (+) RS485A, RS485 differential signal+ RS485-1 (–) RS485B, RS485 differential signal– Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 77 MBUS CCO module has been connected to this port. ● JX01 ports 7, 8, 9, 10, 11, and 12 on the SmartACU2000D-D-03 can be connected to the RS485 cable. ● JX01 ports 7, 8, 9, 10, 11, and 12 on the SmartACU2000D-D-01 can be connected to the RS485 cable only after the SmartModule is installed.
  • Page 78: Optional) Connecting The Peripheral Network Cable

    5.9 (Optional) Connecting the Peripheral Network Cable Connect peripheral network cables to ports FE2 to FE5 on the switch. All network cables can be connected in the same way. Step 1 Prepare a network cable. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 79 Verify that the network cable functions properly using a network cable tester. Step 2 Connect the peripheral network cable to the FE2 port on the switch. Step 3 Bind the network cable. Figure 5-21 Connecting a network cable ----End Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 80: Optional) Connecting The Dc Output Power Cable To The 24 V Power Module

    Step 3 Bind the cable. Figure 5-23 Connecting a DC output power cable to the 24 V power module ----End 5.11 Connecting the Single-Phase Power Cable Step 1 Prepare a cable. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 81: Connecting Do/Di/Ai Cables

    DI, and AI cables. Cabling routes are provided for the signal cables. SmartPID2000 For details about how to prepare and connect the cables, see the User Manual and SmartLogger3000 User Manual . Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 82 SmartACU2000D Smart Array Controller User Manual (With PID Modules) 5 Electrical Connections Figure 5-26 Cabling routes Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 83: System Commissioning

    The cabinet interior is clean, without dust, dirt, or foreign matter. The paint on the cabinet exterior is intact. If paint flakes off, repaint that area to prevent corrosion. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 84: Powering On The System

    Step 5 Turn on the PID switch in the SACU. ● Turn on QF01 for the SmartACU2000D-D-01. ● Turn on QF01 and QF02 for the SmartACU2000D-D-03. Step 6 Turn on the three-phase input switch in the SACU. ● Turn on FU01 for the SmartACU2000D-D-01.
  • Page 85: Powering Off The System

    Step 4 Turn off the three-phase input switch in the SACU. ● Turn off FU01 for the SmartACU2000D-D-01. ● Turn off FU01 and FU02 for the SmartACU2000D-D-03. Step 5 Turn off the PID switch in the SACU. ● Turn off QF01 for the SmartACU2000D-D-01.
  • Page 86: System Maintenance

    ● There is no dust or dirt in the SACU. System running ● All devices in the SACU operate properly. Once every six status months ● The SPD works properly. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 87: Troubleshooting

    3. Contact the dealer or 2. The power grid is Huawei technical support. disconnected from power. 3. The PID module is faulty. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 88 AC socket. 4. The power adapter is faulty. 4. Replace the power adapter. 5. The SmartLogger is faulty. 5. Contact the dealer or Huawei technical support. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 89 If not, set the IP address again. 4. Connect the PC to the Ethernet switch and ping the IP address of the SmartLogger. If the communication is abnormal, replace the network cable and try again. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 90: Component Replacement

    ● If an SPD is damaged or its indication window is displayed in red, replace the SPD. ● A single-phase SPD is replaced in the same way as a three-phase SPD. This section describes how to replace a single-phase SPD. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 91: Replacing The Knife Fuse Switch

    Figure 7-2 Installing a new surge protection module ----End 7.3.2 Replacing the Knife Fuse Switch Step 1 Disconnect the cables from the knife fuse switch and label the cables. Step 2 Remove the faulty knife fuse switch. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 92: Replacing The Fuse Of A Knife Fuse Switch

    Step 4 Connect the cables based on their labels. ----End 7.3.3 Replacing the Fuse of a Knife Fuse Switch Step 1 Open the knife fuse switch box and remove the faulty fuse. Figure 7-4 Removing a faulty fuse Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 93: Replacing The Single-Phase Input Switch

    7.3.5 Replacing the SmartMBUS CCO Module Step 1 Disconnect the cables from the SmartMBUS CCO module and label the cables. Step 2 Remove the faulty SmartMBUS CCO module and its mounting ears. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 94: Replacing The Smartlogger

    Step 5 Connect the cables based on their labels. ----End 7.3.6 Replacing the SmartLogger Step 1 Disconnect the cables from the SmartLogger and label the cables. Step 2 Remove the faulty SmartLogger and its cabinet-mounting bracket. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 95 User Manual (With PID Modules) 7 System Maintenance Figure 7-7 Removing a faulty SmartLogger Step 3 Remove the mounting ears and guide rail–mounting bracket from a new SmartLogger, and install the cabinet-mounting bracket. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 96: Replacing The Smartmodule

    Step 5 Connect the cables based on their labels. ----End 7.3.7 Replacing the SmartModule Step 1 Disconnect the cables from the SmartModule and label the cables. Step 2 Remove the faulty SmartModule and its cabinet-mounting bracket. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 97 User Manual (With PID Modules) 7 System Maintenance Figure 7-9 Removing a faulty SmartModule Step 3 Remove the mounting ears and guide rail–mounting bracket from a new SmartModule, and install the cabinet-mounting bracket. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 98: Replacing The Power Adapter

    Step 5 Connect the cables based on their labels. ----End 7.3.8 Replacing the Power Adapter Step 1 Disconnect the cables from the power adapter and label the cables. Step 2 Remove the faulty power adapter. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 99: Replacing The Pid Module

    Step 1 Open the PID cabinet door and adjust the support bar. Figure 7-12 Adjusting a support bar Step 2 Open the maintenance compartment door of the PID module, and remove the cover from the connection box. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 100 Step 3 Disconnect cables from the faulty PID module and label the cables. Step 4 Remove the pipe connector from the faulty PID module. Step 5 Remove the faulty PID module. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 101 Step 11 Install the support bar and close the PID module cabinet door. NO TE After ensuring that the PID module is powered on, set parameters by referring to the SmartLogger3000 User Manual . ----End Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 102: Replacing The Pid Module Switch

    7.3.11 Replacing the Fiber Adapter Step 1 Disconnect the cables from the fiber adapter and label the cables. Step 2 Remove the faulty fiber adapter. Figure 7-16 Removing a fiber adapter Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 103: Replacing The Usb Port

    Figure 7-17 Removing a USB port Step 3 Install a new USB port. Ensure that the rubber ring is on the inner side of the cabinet. Step 4 Connect the cables based on their labels. ----End Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 104: Technical Specifications

    Operation and Operated and maintained from the front maintenance mode Operating Indoor and outdoor environment Maximum 4000 m (13123.36 ft) operating altitude Installation mode Installed on a support, pole, or wall Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 105 –40°C to +60°C (–40°F to +140°F) temperature Storage –40°C to +70°C (–40°F to +158°F) temperature Note a: Supports a 24 V power module. DC input and output: 24–28 V DC; 70 W (maximum) Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 106: A Scenario Where A Longitudinal Encryption Device Is Used

    ● The longitudinal encryption device, fiber ring network switch, and auxiliary power supply are prepared by the customer based on actual requirements. Huawei device faults caused by any of the three components are not covered by the warranty. ● For details about the installation method and cable specifications, see the installation guide of the components.
  • Page 107 This document provides only the recommended cable routing solution for the longitudinal encryption device, fiber ring network switch, and auxiliary power supply. For details about the cable specifications, see the installation guide of the purchased components. Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 108 SmartACU2000D Smart Array Controller A Scenario Where a Longitudinal Encryption Device User Manual (With PID Modules) Is Used Figure A-2 Installation position and cable routing Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 109 CAT 5E Category 5 enhanced central controller customer-premises equipment direct current digital input digital output environmental monitoring instrument Ethernet Long Term Evolution MBUS monitoring bus Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.
  • Page 110 User Manual (With PID Modules) B Acronyms and Abbreviations protective earthing potential induced degradation power over Ethernet relative humidity small form-factor pluggable surge protective device WEEE waste electrical and electronic equipment Issue 05 (2023-09-26) Copyright © Huawei Technologies Co., Ltd.

Table of Contents