AC connection
Phase connection via two terminals with two holes
E
B
C
A.
M12 DIN 933 screw.
B.
M12 NFE-25 511 M washer.
C.
Terminal. Diameter of the M12 hole, maximum thickness of 10 mm, maximum width of 33 mm, vertical
distance between holes of 44.5 mm.
D.
Busbar.
E.
M12 DIN 934 nut.
Neutral connection via a terminal with one hole
D
A.
M6 DIN 934 nut.
B.
M6 NFE-25 511 M washer.
C.
Terminal. M6 hole diameter, maximum thickness of 10 mm, maximum width of 33 mm.
D.
Busbar.

16.4.2. AC phases connection process via a terminal

Proceed in the following order for each phase:
1.
Clean the contact surfaces on both the terminal and the busbar with a clean cloth and ethanol.
ABQ2026IQE01_A - Installation and Operation Manual
D
C
C
B
B
A
A
Ingeteam
109