Look for different temperatures between similar points (the three AC phases, for example). Differences in
temperature greater than 10 ºC between similar points are considered abnormal.
If there is are abnormal measurements, contact Ingeteam.
Display and LED and led status (check, with voltage)
Check that the Display characters can be properly viewed, along with the access to the different menus.
Check that the LEDs light up correctly.
Voltage and current values (check, with voltage)
Check that the voltage and current values measured by the equipment are correct.
Firmware version of the unit and display (check, with voltage)
Access the Inverter data via the display menu.
The field Firm indicates that the unit´s firmware version. The field FirmDis indicates that the display´s firmware
version.
Check with Ingeteam if there are available updates of both firmware versions.
INFO
For more information on the firmware update process for the unit and display, see the video Firmware upgrade
in the videos section of the INGECON SUN Training website (http://www.ingeconsuntraining.info/?page_
id=3269). The access data are:
Username: powermaxb
Password: Manual

22.3. Preventative replacement tasks

Preventative replacement tasks aim to replace components prior to their loss of function.
Preventative replacement tasks
Element
Fans
Motorized switch
Air filters
AC thermomagnetic circuit breaker
156
11:23
11:23
30/10/15
30/10/15
Replacement frequency
10 years
3000 operations
2 years or deterioration
12,500 operations
ABQ2026IQE01_A - Installation and Operation Manual