19.6.4. Settings

In this menu you can make the following settings:
Date & time
Languages
Modbus ID
Partial deletion
Strings settings
Power settings
Test fans

Autotest

Local command
19.6.5. Autotest
Autotest allows for the grid voltage and frequency limits to be tested automatically, checking that the unit
disconnects correctly within the time set by standard. This menu is only available for some standards, such as CEI
0-21 SPI INTERNO, CEI-0-16 or DEWA INTEGRATED IPS.
During autotest, the disconnection time of the following protections is tested:
Fmax (81>.S1)
Lowest upper limit of the frequency protection.
Fmin (81<.S1)
Highest lower limit of the frequency protection.
Fmax (81>.S2)
Highest upper limit of the frequency protection.
Fmin (81<.S2)
Lowest lower limit of the frequency protection.
Vmax (59.S1)
Lowest upper limit of the voltage protection.
Vmax (59.S2)
Highest upper limit of the voltage protection.
Vmin (27.S2)
Lower limit of the voltage protection.
There are three different states:
Non eseguito
No autotest running and none has been performed during the time in which the inverter has
been switched on.
Riconnessione
State awaiting reconnection for the next measurement after an Fmax, Fmin, Vmax or Vmin
check.
Completato
A full autotest has been carried out during the time in which the inverter has been switched on.
Press
on Avviare Autotest to start autotest. Access Risultati to consult the results of the different tests, observing whether the result is
correct or incorrect. An autotest can be stopped when running by pressing
The results screens for an autotest are then displayed if the test has been completed and a second case in which
the test has not been completed:
132
To modify the date and time of the inverter.
Selection of the language for the text on the inverter display.
Assignation of a number that identifies the inverter. In installations with more than one
inverter, each one must be assigned a different number. Ingeteam recommends using
correlative numbering.
Deletes the partial meters.
Not applicable.
Reduce the unit power.
By accessing this option it is possible to run a test to check the inverter fans are working
properly.
This menu is only available when the standard selected is CEI 0-21 SPI INTERNO,
CEI-0-16 or DEWA INTEGRATED IPS.
The autotest enables an automatic verification of the grid voltage and frequency limits,
bringing these limits toward the real value of the measurement and ensuring that the
unit disconnects in the set time when the measurement does not comply with the limit.
This menu is only available when the standard selected is CEI 0-21 SPI INTERNO,
CEI-0-16 or DEWA INTEGRATED IPS.
From this menu you can change the bottom and top frequency limits. These limits must
correspond to the selected standard.
on Eseguire Autotest.