Ingeteam INGECON SUN PowerMax TL B Series Installation And Operation Manual page 97

Table of Contents

Advertisement

Connection options
CAUTION
The maximum length permitted for the wiring of this contact is 10 meters. If necessary to use longer wiring, add
an intermediate relay as shown in the following figure.
To make the connection, follow the following steps:
1.
Strip the cables.
2.
Crimp the wire ends according to the wire gauge being used.
3.
Open the terminal. The terminals used in this terminal strip are of the clamp type. To insert the cable into
the desired position press with a flat head screwdriver, insert the cable and then remove the screwdriver.
4.
Remove the vertical link.
ABQ2026IQE01_A - Installation and Operation Manual
ETAP
New relay
Ingeteam
97

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents