Connecting An External Power Supply Service - Ingeteam INGECON SUN PowerMax TL B Series Installation And Operation Manual

Table of Contents

Advertisement

Ingeteam
4.
Open the terminal. The terminals used in this terminal strip are of the clamp type. To insert the cable into the
desired position press with a flat head screwdriver, insert the cable and then remove the screwdriver. The
phase is wired at -XAUX.1 and neutral at -XAUX.2.

11.5. Connecting an external power supply service

To avoid the Qdc switch not tripping in the event an auxiliary power failure, Ingeteam recommends installing an
external power supply system.
The external supply system must meet the following specifications:
The system must be connected to terminals -X50 in the DCAC connections module.
To perform the connection correctly, follow the indications in the following table.
80
Auxiliary power supply system
Voltage
Frequency
Power
X50
1 2
Connecting auxiliary services
230 Vac
50/60 Hz
≥ 3500 W
ABQ2026IQE01_A - Installation and Operation Manual