Ingeteam INGECON SUN PowerMax TL B Series Installation And Operation Manual page 70

Table of Contents

Advertisement

Ingeteam
1.
Connect the grounded pole of each unit through a 35 mm
This connection can be done through the cable grommets provided in the bases of the units in question.
Inverter 1
2.
Connect the CAN communication buses from both inverters using the cable provided. To connect the
communication buses, carry out the following process:
On the inverter where the grounding kit (-TSGND) is being installed, remove the end of line resistor
from the wiring between -X26.3D and -X26.4D and connect the CAN cable with the color code
described in the diagram to -X26.1C, -X26.2C, -X26.3C, -X26.4C.
70
Inverter 1
CAN
Connection of the PV array grounding kit [optional]
section cable with 1000/1500 V insulation.
2
Inverter 2
Inverter 2
ABQ2026IQE01_A - Installation and Operation Manual