19.2. Display

A.
Current date, YYYY-MM-DD.
B.
Power reduction percentage and reason for this reduction*.
C.
Current time, hh:mm. If there is a loss of communication between the inverter and the display, the two
points stop blinking.
D.
Voltage and power of the PV array. Both pieces of data are displayed alternately.
E.
Power, voltage and current fed to the grid.
F.
Wattmeter for instantaneous self consumption. This symbol is only displayed if the inverter is configured
to work in self consumption mode. If it flashes, this is due to a communication failure with the wattmeter.
Pressing the key
takes you to the main menu. Pressing the key
displays the energy graph for the last 24 days.
* The reasons for power reduction are as follows:
T: Temperature. The inverter is limiting the power due to internal overheating.
C: Communications. The inverter is limiting the power after having received a reduction setpoint through
communications.
F: Grid frequency. The inverter is limiting the power due to the grid frequency variation.
V: Grid voltage. The inverter is limiting the power due to the grid voltage variation.
Q: Reactive priority. The inverter is limiting the power due to the injection of reactive power.
A: Configuration. The inverter is configured to limit its power.
R: Initial connection ramp. The inverter is limiting the power after a reconnection to the grid.
S: Self consumption mode. The inverter is limiting the power due to functioning in self consumption
mode.
M: Reserved mode.
124
A
B
2018/07/09
2018/07/09
D
C
11:23
11:23
F
E
displays the daily power graph. Pressing
ABQ2026IQE01_A - Installation and Operation Manual