Mounting Conditions, Internal Cooling - Siemens 6SN1123-1AA00-0DA2 Configuration Manual

Simodrive 611 series drive converter
Table of Contents

Advertisement

05.08
05.01
9.1.2

Mounting conditions, internal cooling

Note
The regulations described in the "SINAMICS S120 Booksize / SIMODRIVE
System Manual" switchgear cabinet integration system manual
Order No.: 6SL3097–0AT00–0APV must be observed for the heat dissipation!
General
If the guidelines for installing/mounting SIMODRIVE 611 equipment in the cabi-
information
net are not carefully observed, this can significantly reduce the service life of the
equipment and result in premature component failure.
The following specifications must be carefully observed when mounting/instal-
ling a SIMODRIVE 611 drive group:
S
S
S
Cooling clearance
Minimum 100 mm clearance at the top and bottom for cooling.
Incorrect
80 mm
Ä Ä Ä
Ä Ä Ä
40 mm
SIMODRIVE 611
40 mm
Ä Ä Ä
Ä Ä Ä
Fig. 9-4
Cooling clearance
Air intake temperature, max 40 °C, at higher temperatures (max 55 °C), the
power must be reduced (derating).
© Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
9.1 Installation and connecting–up regulations
Cooling clearance
Cable routing
Air flow, climate–control equipment
100 mm
Channel cable
100 mm
9 Cabinet Design and EMC
Correct
Ä Ä Ä
Ä Ä Ä
Cooling clearance
SIMODRIVE 611
top and bottom
100 mm
Ä Ä Ä
Ä Ä Ä
9
9-341