Indirect Position And Motor Speed Sensing; 3.4 Direct Position Sensing; Encoder Systems That Can Be Evaluated - Siemens 6SN1123-1AA00-0DA2 Configuration Manual

Simodrive 611 series drive converter
Table of Contents

Advertisement

3 Motor Selection, Position/Speed Sensing

3.4 Direct position sensing

3.3

Indirect position and motor speed sensing

3.4
Direct position sensing
3.4.1

Encoder systems that can be evaluated

Recommended
encoder signals
for fault–free
operation with
sin/cos 1 Vpp
Parameterizable
encoder limit
frequency
(as of SW 5.1.14)
3-68
The various possibilities for indirect position and speed sensing and to position
the motor shaft as a function of the drive configuration (SINUMERIK,
SIMODRIVE and Motor) are shown in Table 3-6 (Chapter 3.5).
The various possibilities for direct position sensing for positioning as a function
of the drive configuration (SINUMERIK, SIMODRIVE and Motor) and the en-
coder system being used are shown in Table 3-7 (Chapter 3.5).
As a result of the higher data transfer reliability, we recommend that sinusoidal
voltage signals are used.
The following encoder signals are recommended for fault–free operation:
⇒, refer to Chapter 3.2 "Motor encoders"
Machine data MD 1326: $MD_SAFE_ENC_FREQ_LIMIT can be used to para-
meterize a limit frequency. The maximum value is 420 kHz, the lower limit and
default value is 300 kHz.
Note
Changes to this MD may only be made carefully taking into account the
prevailing conditions.
This functionality is only supported by SIMODRIVE 611 digital High
Performance control units.
Table 3-1
Encoder limit frequency and speed
Encoder pulses/
rev.
2048
5800 RPM
1024
11600 RPM
512
22200 RPM
The following secondary conditions/limitations are specified:
1. Cable to be used:
Siemens cable, Order No.: 6FX2002–2CA31–1CF0
2. Maximum permissible encoder cable length:
Encoder limit frequency 420 kHz: 20 m
3. Encoder characteristics: "–3dB cut–off frequency" greater than or equal to
500 kHz
Examples of encoders that can be used:
ERA 180 with 9000 pulses/rev and ERA 180 with 3600 pulses/rev from the
Heidenhain Company.
4. The amplitude monitoring that is active up to 420 kHz.
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
Speed at the maximum encoder limit frequency
200 kHz
300 kHz
8700 RPM
17400 RPM
34800 RPM
© Siemens AG 2012 All Rights Reserved
02.07
05.01
420 kHz
12300 RPM
24600 RPM
49200 RPM