Siemens 6SN1123-1AA00-0DA2 Configuration Manual page 14

Simodrive 611 series drive converter
Table of Contents

Advertisement

02.12
05.01
!
© Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
Note
The terminal blocks of the SIMODRIVE 611 modules are used for electrical
connection of the particular module. If the terminal blocks are used for another
purpose (e.g. to carry the module), this can damage the module. If the
insulation is damaged, then this can cause injury due to electric shock.
Note
For a minimum fault current, the machine manufacturer must ensure that the
upstream overcurrent protection devices trip within 5 s (see Chapter 7.3; Table
7–5 and Fig. 7–8
Note
The following secondary conditions/limitations must be carefully observed if the
machine is subject to a high–voltage test:
1. Power–down the unit.
2. Withdraw the overvoltage module in order to prevent the voltage limiting
responding.
3. Disconnect the line filter so that the test voltage does not dip.
4. Connect M600 to PE through resistor 100 kΩ (the grounding clip in the NE
modules is open). In the factory, the units are subject to a high–voltage test
at 2.25 kV
phase–PE. The NE modules are shipped with the grounding
DC
clip open.
5. The maximum permissible voltage for a high–voltage machine test is
1.kV
phase–PE.
DC
Danger
The control and drive components for a power drive system (PDS) are allowed
for industrial and commercial use in industrial networks. Their use in public
networks requires a different configuration and/or additional measures.
Forword
xiii

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents