Danger
1) Notice!
Do not use for module widths 50 – 200 mm.
Danger of death because the contact safety is
endangered!
Fig. 6-20
Mounting location for the capacitor modules
Depending on the line infeed used, several capacitor modules can be con-
nected in parallel.
For the capacitor modules with 2.8 mF and 4.1 mF, the total charge limit of the
line infeed may not be exceeded (refer to Chapter 1.3).
Capacitor modules
The capacitor modules 2.8 mF and 4.1 mF (central/distributed) must be dimen-
that can be
sioned/selected corresponding to the engineering table 1-4 in Chapter C.1.1
taking into account the charge limits of the infeed.
connected
The 20 mF capacitor modules do not have to be taken into account in the 1-4
engineering table. They must be selected as required taking into account the
maximum number from Table 6-19.
Table 6-19
UI 5 kW
UI 10 kW
I/R 16 kW
UI 28 kW
I/R 36 kW...120 kW
1) Valid if all of the monitoring modules used are connected to the AC line supply.
© Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
Central module with 20 mF (width: 300 mm)
PM
100
Central module with 4.1 mF (width: 100 mm)
Distributed module
Maximum number of 20 mF capacitor modules
Infeed unit
6 Infeed Modules
6.7 DC link options
Adapter terminals, Order No.
for module width 50 – 200
mm 6SN1161–1AA01–0BA0
for module width 300 mm
6SN1161–1AA01–0AA0
Cable length,
max. 5 m
Note:
+
The distributed
capacitor modules
may only be
mounted and
installed vertically.
Maximum that can be connected
1
3
5
1)
6
1)
6-189