Interfaces And Terminals - Siemens 6SN1123-1AA00-0DA2 Configuration Manual

Simodrive 611 series drive converter
Table of Contents

Advertisement

5 Power Modules

5.6 Interfaces and terminals

5.6
Interfaces and terminals
5.6.1
Interface overview
Table 5-5
1–axis module
Term.
Designa-
Function
no.
tion
U2
A1
Motor connection
V2
W2
PE
Protective conductor
Protective conductor
P600
DC link
M600
DC link
Table 5-6
2–axis module
Term.
Designa-
Function
no.
tion
U2
A1
Motor connection for axis 1
V2
W2
U2
A2
Motor connection for axis 2
V2
W2
PE
Protective conductor
P600
DC link
M600
DC link
1) O = Output; I = Input
5-136
Type
1)
O
I/O
I/O
Type
1)
O
O
I/O
I/O
Note
For 2–axis module, Order No.: 6SN1123–1AB00–0CA2/0CA3, note that the
terminal arrangement of A1 and A2 differs compared to the other 2–axis
modules!
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
Typ. voltage/limit values
3–ph. 430 V AC
0 V
0 V
+300 V
–300 V
Typ. voltage/limit values
3–ph. 430 V AC
3–ph. 430 V AC
0 V
+300 V
–300 V
© Siemens AG 2012 All Rights Reserved
05.08
10.04
11.05
05.01
Max. cross–section
See Chapter5.6.2
2 screws
Busbar
Busbar
Max. cross–section
See Chapter5.6.2
See Chapter5.6.2
2 screws
Busbar
Busbar