7 Line Supply Connection
7.2 Voltage matching
Connection types
Example:
TN–C line supply
TN–C line supply direct connection schematic
Line supply/transformer for the factory
Z
Line filter
Commutating
reactor
U1 V1 W1
NE module
Fig. 7-3
TN–C line supply connection schematic
TN–C line supply
TN–S line supply
TN–C–S line
supply
1)
Harmonized transformer types are described in Siemens Catalog NC 60.
7-206
The infeed can be directly connected to a TN line supply for 3–ph. 400 V AC,
3–ph. 415 V AC, 3–ph. 480 V AC
For other voltage levels, the infeed can be connected through an autotrans-
former.
TN–C line supply with autotransformer direct connection
schematic
Line supply/transformer for the factory
L3
L2
L1
N (5 conductor)
PEN
Autotransformer
Commutating
reactor
PE
Symmetrical 4–conductor or 5–conductor three–phase line supply with
grounded neutral point with a protective and neutral conductor connector con-
nected at the neutral point which, depending on the line supply type, uses one
or several conductors.
For other line supply types
an isolating transformer.
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
N
Z
Line filter
PE
U1 V1 W1
NE module
1)
the NE module must be connected through
© Siemens AG 2012 All Rights Reserved
02.12
05.01
L3
L2
L1
PEN