5 Power Modules

5.3 Technical data

5.3
Technical data
General
Definition of the
currents
Definition of the
power ratings
5-124
The technical data of the power modules is specified in Table 5-1 for the 1–axis
version and in Table 5-2 for the 2–axis version.
The specified values are valid for:
S
The specified rated frequency (inverter pulse frequency)
S
Maximum ambient temperature of 40 °C
S
Installation altitude<1000 m above sea level
Derating must be applied for conditions that deviate from those specified above.
The power modules do not have any overload protection, but only a current
acquisition without its own processing. The overload protection is realized in the
SIMODRIVE 611 control unit.
Also refer to the definition of the load duty cycles (Fig. 5-2 to 5-5)
S
FD mode
– I
Continuous nominal current, rated current
n
– I
Peak current
max
S
Operating modes, MSD–IM and MSD–SRM
– I
Continuous nominal current, rated current
n
– IS6–40%
Current for maximum of 4 min. for the S6 load duty cycle
– I
Peak current
max
– I
Minimum motor current
min
– n
Speed at the start of field weakening
FS
– I
Motor no–load current in A
0Mot
The following restrictive conditions must be met:
for induction motors:
– The no–load current of the motor (I
rent of the power module (according to Table 5-1).
– On the basis of the actual current value resolution, the lowest occurring
no–load current of the motor must satisfy the following condition:
n
FS

w
I
n
0Mot
max
for synchronous motors:
A ratio of I
max_powersection
synchronous motors.
Appropriate values are specified in Table 5-1 and 5-2 to dimension the cabinet
cooling. These are defined as follows:
S
P
Total power loss dissipated by the module
Vtot
S
P
Power loss that can be dissipated externally or using
Vext
hose cooling
S
P
Power loss that cannot be dissipated using hose cooling or
Vint
external cooling (this power loss remains in the control cabinet)
For components with internal cooling, the complete dissipated power loss re-
mains in the control cabinet.
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
rms
) must be less than the rated cur-
0Mot
I
(I
according to Table 5-1)
min
min
X 5 should not be exceeded for
/I
0_100K (motor)