6 Infeed Modules
6.4 Technical data
Supply voltage
and frequency
Table 6-8
Supply voltage and frequency
NE-Module
Line voltage: U1, V1, W1
With derating P
and P
rated
max
DC link voltage
Frequency
1) See Table 6-9, Technical data I/R modules
This means that the operational reliability is increased even when connected to weak line supplies!
6-166
Switches S1.1 and S1.4 (see Chapter 6.3) are used to adapt the line infeed mo-
dules to the prevailing line supply conditions.
The converter system is designed for operation on grounded line supplies TN–S
and TN–C (IEC 60364–1 VDE 0100–300). For other line supply types, a trans-
former with separate windings in vector group yn on the secondary side must be
connected upstream (refer to Chapter 7 for the dimensioning).
S1.1, S1.4 = OFF
Un = 3AC 400 V
3AC 400 V " 10%
3AC 380 V " 15%
1)
DC 600 V
45...65 Hz
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
S1.1 = ON
Un = 3AC 415 V
Un = 3AC 480 V
3AC 415 V " 10%
3AC 480 V + 6% –10%
DC 625 V
© Siemens AG 2012 All Rights Reserved
02.12
05.01
S1.4 = ON
DC 580...710 V
55...65 Hz