05.08
05.01
Fig. 9-3
Shield connection 6SN1162–0FA00–0AA1
The shields of original pre–assembled cables are automatically connected
when the cable is plugged–in.
Exceptions:
Shield connection
In order to ensure a good connection between the front panel and the housing,
front panel
the screws at the front panel must be tightened with a torque of 0.8 Nm.
© Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
9.1 Installation and connecting–up regulations
Shield connection (6SN1162–0FA00–0AA1)
Retaining clip for the shield
Terminal clamp for busbars 10x3 mm
4–fold shield connection (6SN1162–0FA000AA2)
– Setpoint cable from the analog NC
Here, the shields of the setpoint pairs must be connected to the upper
side of the module. The threaded sockets provided can be used for this
purpose (M5x10/3 Nm).
– Drive bus cable from SINUMERIK 840C
Here, the shield is connected to the threaded socket mentioned above
using the clamp provided.
– Drive bus and equipment bus extension cables for 2–tier configurations.
Here, shields are connected at both ends of the cables to the above
mentioned threaded sockets using the clamps provided.
– Motor power cables
The shields of the motor feeder cables are connected, using the hose
connectors provided, to the shield connecting plates (accessories) of the
modules.
9 Cabinet Design and EMC
Refer to
Chapter 12
9-339