10.2.
Fieldbus address (slave address), baud rate, parity and monitoring time: set
Information
10.3.
Open switch compartment
SAR 16.2 Control unit - electromechanical
6.
Press
Edit.
Display indicates: ▶ Specialist (4)
7.
Use
Up ▲ Down ▼ to select user:
Information: Required user level: Specialist (4) or higher
The symbols have the following meaning:
-
black triangle: ▶ = current setting
-
white triangle: ▷ = selection (not saved yet)
8.
Press
Ok.
Display indicates: Password 0***
9.
Enter password (→ enter password).
The screen indicates the pre-set type of seating (▶Limit or ▶Torque) by means
of a black triangle ▶.
10. Use
Up ▲ Down ▼ to select new setting.
The symbols have the following meaning:
-
black triangle: ▶ = current setting
-
white triangle: ▷ = selection (not saved yet)
11. Confirm selection via
The setting for the type of seating is complete.
12. Back to step 4 (CLOSED or OPEN): Press
Customer settings M0041
Modbus M0341
MD1 slave address M0247
MD2 slave address M0409
Baud rate M0343
Parity/stop bit M0782
Monitoring time M0781
Default values:
MD1 slave address = 247
MD2 slave address = 247
Baud rate = Auto
Parity/stop bit = Even, 1 stop bit
Monitoring time = 15 seconds
Parameter MD2 slave address is only available if AUMA redundancy I (option) is
available.
For further settings and information e.g. on redundancy, refer to Manual (Device
integration).
The switch compartment must be opened to perform the following settings.
Commissioning (basic settings)
Save.
Esc.
55