Detector Status Display
1.
Set the detector as follows:
2.
Operate detectors continuously for 90 days with all environmental factors (such as,
temperature, humidity, air flow, occupancy, and so on) similar to the intended application for
the detectors. Record all events for each tested detector with an electronic History buffer or a
printout.
3.
At the end of the 90-day test: An authorized Notifier representative, or an end user trained by
an authorized Notifier representative must inspect the results of the test. If the test results show
no alarms or pre-alarms for the tested detectors, reprogram the fire alarm system to set the
Alarm sensitivity to the more sensitive Pre-Alarm level of the test.
D.5 Detector Status Display
D.5.1 Detector Maintenance Display
Should the panel detect a low chamber value or maintenance condition with a detector, it will
generate a point trouble as described in the operations manual for this panel. The following Read
Status screen displays detector information that applies to the state of the smoke detector. It can be
reached with the following commands, starting at the Main Menu screen:
Press MAIN MENU
Press READ STATUS
Press READ STATUS POINT SELECT (enter the detector point address)
Press ACCEPT
D.5.2 Print a Detector Maintenance Report
A Detector Maintenance Report lists detector maintenance status for each installed addressable
detector [except FDX (an analog heat detector)].
NFS2-3030 Programming Manual — P/N 52545:A 11/29/2005
Step
Action
1
Initially set to the 0.50% obscuration per foot Alarm level.
2
Set the Pre-Alarm level to the desired final Alarm sensitivity.
3
Set the Pre-Alarm to Alert mode (non-latching).
L A K E V I E W G E N E R A L H O S P I T A L
S Y S T E M N O R M A L
1 0 : 2 2 : 3 4 A
F R I S E P 2 3 , 2 0 0 5
R E A D A D D R E S S :
A U T O M A T I C
I N A C T I V E
E L E V A T O R L O B B Y
F I F T H F L O O R
Z 0 0 5 ,
Z 0 2 7 ,
,
,
V A L U E S : 0 1 1 % O F A L A R M , 0 4 5 % O F P R E A L A R M
A L A R M : 6 = 1 . 6 6 % , P R E A L A R M : 3 = 0 . 4 7 %
A C T I O N / S T A T U S : N O N E / V E R Y C L E A N
P E A K S : 5 6 % V E R I F Y C O U N T : 0 2 C O - O P : D 1 0 0 , 1 5 8
1 0 : 2 2 : 3 4 A
Figure D.6 Smoke Detector Screen - Read Status
Intelligent Sensing Applications
L 0 3 D 0 5 2
E A S T W I N G
Z 0 0 3
S M O K E ( P H O T O )
Z 0 6 6 ,
,
,
,
F R I S E P 2 3 , 2 0 0 5
,
,
B A C K
115