Programming
SYSTEM SETUP

1=TIMERS

2=BANNER
3=TIME-DATE
System Setup Screen #1
TIMERS
1=PAS DELAY
120
2=PRE SIGNAL
120
3=WATERFLW DELAY
0
Timer Screen #1
76
Timers
Timer delays for PAS, Pre-signal and waterflow activation can be programmed by pressing 1 while
viewing System Setup Screen #1. The following screen will be displayed:
1=PAS DELAY
2=PRE SIGNAL
3=WATERFLW DELAY
1=AC LOSS DELAY
PAS (Positive Alarm Sequence) Delay
The factory default setting for PAS is 000 for no delay. To select a PAS delay of 001 to 180 seconds
for all devices programmed for PAS, press 1 while viewing Timer Screen #1. The following dis-
play will appear:
RANGE 000-180 SECONDS
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting
of three digits, such as 005 for five seconds. Upon entering the third digit, the time delay will be
stored in the control panel memory and the display will return to the Delay Screen which will indi-
cate the new delay time.
Pre-signal Delay
The factory default setting for Pre-signal delay is 000 for no delay. To select a Pre-signal delay of
001 to 180 seconds for all devices programmed for Pre-signal, press 2 while viewing Timer Screen
#1. The following screen will be displayed:
RANGE 000-180 SECONDS
TIMERS
Timer Screen #1
TIMERS
Timer Screen #2
PAS DELAY
PAS Delay Screen
PRESIGNAL DELAY
Pre-signal Delay Screen
MS-5UD & MS-10UD Series Manual — P/N 52626:C2 1/24/2012
Master Programming Level
120
120
0
2