Appendix F: Wire Requirements

Connecting external system accessories to the main circuits must be carefully considered to ensure
proper operation. It is important to use the correct type of wire, gauge and run length for each
circuit. Reference the chart below to specify wire requirements and limitations for each circuit.
CIRCUIT CONNECTIONS
Circuit Type
Circuit Function
Initiating Device
Connects to
Circuit
Initiating Devices
(power-limited)
ANN-BUS (EIA-485)
Communication for
power-limited
ANN-BUS
annunciator and
relay modules
ANN-BUS Power
Power for
ANN-BUS
annunciators
24 VDC Regulated,
Power for
resettable,
accessories and
nonresettable
4-wire devices
Auxiliary Trouble
Open Collector
Input
trouble input for
CHG-75,
CHG-120, etc.
NAC/Solenoid
Connects to NAC
Outputs
devices or Release
devices
150
Wire Type and Limitations
Untwisted, unshielded wire
or twisted, unshielded wire
(maximum loop resistance
not to exceed 100 ohms)
Twisted pair a maximum
loop resistance of 120 ohms
Refer to Table 2.1, "Wiring Distances," on page 36 for information on device wiring.
Untwisted, unshielded or
twisted pair, unshielded wire
Single conductor
Untwisted, unshielded pair
wire or twisted, unshielded
pair wire
Table F.1 FACP Wire Specifications
WIRE REQUIREMENTS
Recommended
Max. Distance
Feet (meters)
Distance limitation
12-18 AWG (3.25 - 0.75 mm
set by 100 ohm
resistance limitation
6,000 (1,800 m)
12-18 AWG (3.25 - 0.75 mm
Distance limitation
12-18 AWG (3.25 - 0.75 mm
set by 4 volt
maximum line drop
Distance limitation
18 AWG (0.75 mm
20 feet in same
room
Refer to Section F.1 on page 151.
RP-2002 Series Manual — P/N 53039:E6 1/26/2017
Wire Gauge
2
)
2
)
2
)
2
)