Commissioning (Optional Equipment Settings); Potentiometer; Potentiometer Setting; Rwg Electronic Position Transmitter - AUMA SAEx 07.2 Operation Instructions Manual

Hide thumbs Also See for SAEx 07.2:
Table of Contents

Advertisement

Commissioning (optional equipment settings)

11 Commissioning (optional equipment settings)

11.1 Potentiometer

Setting elements The potentiometer is housed in the actuator switch compartment. The switch compart-

11.1.1 Potentiometer setting

How to proceed 1. Move valve to end position CLOSED.

11.2 RWG electronic position transmitter

Technical data
11)
Power supply possible via: AC, AM actuator controls or external power supply
42
The potentiometer is used as travel sensor and records the valve position.
ment must be opened to perform any settings. Refer to
[} 37].
Setting is made via potentiometer [1].
Figure 43: View of control unit
[1]
Potentiometer
Due to the ratio of the reduction gearing, the complete resistance range/stroke
is not always covered. Therefore, external adjustment (setting potentiometer)
must be provided.
2. Turn potentiometer [1] clockwise to the stop.
ð End position OPEN corresponds to 0 %.
ð End position OPEN corresponds to 100 %.
3. Turn potentiometer [1] slightly in opposite direction.
4. Perform fine-tuning of the zero point at external setting potentiometer (for remote
indication).
RWG electronic position transmitter records the valve position. On the basis of the ac-
tual position value measured by the potentiometer (travel sensor), it generates a cur-
rent signal between 0 – 20 mA or 4 – 20 mA.
Table 17: RWG 4020
Data
Output current I
a
11)
Power supply U
V
Max. current consumption
Max. load R
B
Impact of power supply
Load influence
Temperature impact
Open switch compartment
3-wire and 4-wire systems
0 – 20 mA, 4 – 20 mA
24 V DC (18 – 32 V)
24 mA at 20 mA output current
600 Ω
0.1 %/V
0.1 %/(0 – 600 Ω)
< 0.3 ‰/K
[1]
2-wire system
4 – 20 mA
14 V DC + (I x R
), max. 30 V
B
20 mA
(U
– 14 V)/20 mA
V
0.1 %/V
0.1 %/100 Ω

Advertisement

Table of Contents
loading

This manual is also suitable for:

Saex 16.2Sarex 07.2Sarex 16.2

Table of Contents