Function "Fixed Cur. Value" (064), Hart Only; Function "Out Status" (064), Profibus Pa Only - Pepperl+Fuchs Pulscon LTC Description Of Instrument Functions

Guided level radar with hart/4 ma ... 20 ma and profibus pa
Table of Contents

Advertisement

Pulscon LTC
Function group "output" (06), - "profibus param." (06), PROFIBUS PA only
+
E
"
+
E
"
48
8.9

Function "fixed cur. value" (064), HART only

Set the fixed current value with this function. This data is necessary if you have selected
the "fixed current" option in the "curr. output mode" (063) function.
User input:
3.8 mA ... 20.5 mA
Caution!
This user input is available for HART devices only!
8.10

Function "out status" (064), PROFIBUS PA only

Displays the current output status (for value, see operating instructions of relevant
instrument).
Caution!
This function is available for PROFIBUS PA devices only!