Pulscon LTC
Function group "output" (06), - "profibus param." (06), PROFIBUS PA only
+
E
"
+
E
"
+
E
"
46
8.4

Function "ident number" (061), PROFIBUS PA only

manufacturer
profile
manufacturer
Set to XXXX hex according to manufacturer (PNO registered).
profile
Setting defined as in PROFIBUS PA Profile 3.0: 9700 hex - instrument with one
AI block.
Caution!
This function is available for PROFIBUS PA devices only!
8.5

Function "low output limit" (062), HART only

The output of negative level values can be suppressed with this function.
Selection:
off: minimum output -10 % (3.8 mA for HART)
on: minimum output 0 % (4 mA for HART)
OFF
Caution!
This user input is available for HART devices only!
8.6

Function "set unit to bus" (062), PROFIBUS PA only

confirm
After confirming this function, the unit of the measured variable is taken over in the
AI block (PV scale -> out scale). This function must always be executed after changing
the unit.
Caution!
This function is available for PROFIBUS PA devices only!
ON